EAY 1*50

Description

Description

Standards

  • International
    IEC 60227-3; IEC 60228; IEC 60332-1-2

 1-SCOPE

This specification covers single core, PVC insulated cables, intended for internal wiring in dry locations,concealed in conduits.

2.1-Conductor

Aluminum conductors, complying with the applicable requirements of IEC 228.

2.2 - Insulation

PVC based thermoplastic material

 

Test at works IEC 227-3

Routine Tests

 - Max. DC conductors resistance at 20°C acc. to IEC 60227-2 parag.2.1                                    

- Spark test during insulation                                                                     

Liban Cables will carry out these tests on all the length and tests certificates will be provided

 

Sample Tests

                Check of the build - up and color coding of the cable                                                                      

                Check of dimensions                                                                     

                Insulation            :               according to IEC 60227-2  parag. 1.9

These tests will be carried out on one length of each size during each inspection .                            

Tests certificates will be provided by Liban Cables                                                                                            

 

Type Tests

Mechanical characteristics on insulation material (tensile strength and elongation at break  ) in accordance with IEC 60227-3

These tests will be carried out on one length of the order.

Tests certificates will be provided by Liban Cables

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Stranded aluminum
Insulation
PVC

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
50 mm²
Nominal insulation thickness
1.4 mm
Nominal overall diameter
11.0 mm
Approximate weight
185 kg/km

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
0.641 Ohm/km

Usage characteristics

Usage characteristics

Flame retardant
IEC 60332-1-2

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close